Fan monitoring can be triggered in devices with a power greater than 7.5 kW (eliminated from V5.0 onwards)

Eliminated from:
StateLine / HighLine with firmware version V05.01 or higher

Behaviour of the new version?
This function restriction is eliminated with the above-mentioned firmware version.



Which products are affected?
8400 StateLine / HighLine with a power > 7.5 kW and with FW < 05.01

What happens?
'Fan error' is entered into the Logbook.

When does the problem occur?
In a worst case scenario, the fan monitoring can be triggered causelessly in devices with powers from 7.5 kW.

Possible diagnostics?
Control the fan via fan running noises

Short-term measures / recommendations?
Deactivate response to fan failure (C00566)

Evaluation:
If the fan really fails, the inverter will switch off due to overtemperature after a while of being under load. This will not permanently destroy the inverter.

Information taken from chapter 1.1.8 of Service Message No. 16/2010.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201006100/1/