Which products are affected?
EPM-S110 with software version 01
What happens?
At present, the I/O only supports four Rx /Tx PDOs. If further PDOs are activated afterwards, these are sent once but then not any more.
Possible diagnostics?
Check the CAN bus for the telegram mentioned above (e. g. by using the PCAN Explorer)
Short-term measures/recommendations?
If more than four PDOs are required another bus coupler is to be used.