Internal BAD process data status was not evaluated (elimination)

Which products are affected?
E94AYCER FW 0.50 and 1.01 communication module

Description of the problem
The Lenze communication module has imported the process and safety data and processed it internally even though the Profinet controller set the process data status to BAD. The process data words and the Profisafe data all have their own internal process data status that is transferred with the data.

When does the problem occur?
When the process data status of the Profinet controller was set to BAD.

Diagnostics options?
When process and safety data has been processed even though this is not currently permitted.

Short-term measures/recommendations?
None

Evaluation:
As of FW 1.10, this functional restriction has been eliminated. If the communication module receives process and safety data with a BAD status, these are rejected and mull data transferred internally.