Limitation of the field frequency causes the drive to vibrate (remedied from SL:V3.0 HL:V2.0 onwards)

Remedied from:
8400 StateLine  SW V3.00 onwards
8400 HighLine   SW V2.00 onwards

Behaviour of the new version?
The above-named software version rectifies this functional restriction.




Which products are affected?
8400 StateLine  SW ≤ V2.00
8400 HighLine   SW ≤ V1.00

What happens?
If the limiting function of the max. output frequency (L-C00910/1 and L-C00910/2) is active, the drive vibrates.

When does the problem occur?
The problem occurs if the limitation of the max. output frequency is active.

Possible diagnostics?
Observe the output frequency

Short-term measures/recommendations?
None.

Evaluation:
The limitation of field frequency is no standard operating state but a monitoring function. The operating features are not limited in the unlimited state.

Published with service message No. 2009/02