Charging current control, C0031 adjustable threshold for OC1 overcurrent during loading (V4.0 onwards)
Function extension:
Particularly for the purpose of loading an extremely large DC-bus capacity, the trigger threshold for the time-related monitoring of the loading process can now be extended. The monitoring responds (OC1 fault) if the DC-bus voltage has not reached a certain voltage level within a set time (trigger threshold C0031).
Setting range for code C0031: 40...100, equivalent to 400...1000ms.
In which products/versions is it included?
ECS power supply module V4.0 onwards