Error/cycle counter cannot be reset via the Engineer button (remedied from V1.05)

Remedied from:
Communication module E94AYCEP Firmware V1.05

Behaviour of the new version
In combination with Engineer ≥ 2.5 the button to reset the error and cycle counter works.



Which products are affected?
Communication module E94AYCEP Firmware V0.51

What happens?
The values of the error/cycle counters cannot be reset by means of the button provided on the Engineer user interface.

When does the problem occur?
The problem occurs if firmware version 0.51 of the EPL module and Engineer 1.5 are used.

Possible diagnostics?
The behaviour described has appeared if the values do not change although the reset button has been pressed.

Short-term measures/recommendations?
Both counters can be reset manually via the parameter C13881/C14881 and C13882/C14882.

Evaluation:
In the current firmware version 1.05 of the EPL module in combination with Engineer ≥ 2.5 the button works.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200807351/1/