Wrong data type L-C13886 and L-C14886 (remedied from V1.11)

Remedied from?
Communication modules Profibus E94AYCPM FW 1.11

Eliminated function restriction?
The code has the correct data type BITFELD_8



Which products are affected?
Communication modules Profibus E94AYCPM FW 1.00, 1.05 and 1.10

What happens?
The access to this code via Profibus is denied with the error message 'wrong data type'.

When does the problem occur?
When the code is to be changed via the Profibus network.

Possible diagnostics?
When the access to this code via the Profibus network is denied with an error message.

Short-term measures/recommendations?
Address the code via the Unsigned_8 data type.

Evaluation:
As of FW 1.11 the code has the correct data type BITFELD_8.