LEDs are not activated correctly

Which products are affected?
ESP-HMI1-P (HMI Designer V1.7)
EPM-H410 (Graphical display unit)

What happens?
When configuring the H410 it can be specified that the green LED of one of the 24 function keys is switched on when a sequence is activated (see project component 'Sequences').

When a sequence is activated it may happen that in contrast to the configuration any LED or no LED at all is on.

When does the problem occur?
The response described above may occur when a sequence is activated.

Possible diagnostics?
None.

Short-term measures/recommendations?
Activate the LEDs of the keypad via the command area of the keypad. If this is not possible, do not switch on a LED via the activation of a sequence.

Evaluation:
The LEDs of the H410 support the user when controlling and operating the device. Due to the function restriction LEDs should not be switched on via the activation of a sequence. The function restriction can be detected during commissioning at the latest.

 