Signal selection of the oscilloscope is not saved in the drive (remedied from V4.10 SP4)

Remedied from?
GDC V4.10 SP4, GDCeasy V4.10 SP4

Behaviour of the new version?
With SP 4 for GDC version 4.10, the selection of the signals (configured in the Oscilloscope control dialog) to be recorded is transmitted to the drive if the signals have been acknowledged by pressing the <Acceptance> button in the selection dialog.



Which products are affected?
GDC V4.10, GDCeasy V4.10

What happens?
The selection of the signals which are to be recorded by the oscilloscope is not saved in the drive. When GDC is closed and re-opened afterwards, the signals to be recorded must again be selected in the oscilloscope.

When does the problem occur?
The response described above occurs if the signals are selected via the Oscilloscope control dialog of the oscilloscope (button <Control>) and GDC is exited without having started a measurement. The signal is only transmitted to the drive when the measurement is started.

This function restriction only refers to the signal selection. All other parameters from the Oscilloscope control dialog are saved in the device.

Possible diagnostics?
None.

Short-term measures/recommendations?
Select the signals which are to be recorded by the oscilloscope under code C0732/1…4 or in the function block editor (FB OSZ). Thus the settings are saved in the drive.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200805416/1/