AP1 trip after project download (remedied from B-SW V8.0)

Remedied from:
ECS axis module V8.0

Behaviour of new version?
If a user error is active at the beginning of the project download, an AP1 trip is not triggered after the project download.



Which products are affected?
EVS93xxEI (Servo PLC V7.1 and lower)
EVS93xxET (Servo PLC with technology function V7.1 and lower)
ECS axis module V7.4

What happens?
The ECS axis module indicates an AP1 trip (C0168/1 = 41) when a project has been download.

When does the problem occur?
The response described before occurs if a user error has still been pending when the project download is started. User errors can be triggered by means of the L_FWM function block from the LenzeDrive.lib library.

Possible diagnostics?
None.

Short-term measures/recommendations?
If the ECS axis module indicates an AP1 trip carry out mains switching of the ECS axis module in order to reset the trip.

Evaluation:
This function restriction only occurs when a project is downloaded in case of which a user error was pending at the beginning of the download.

Published with service message No. 2008/08 and 2008/09