New signal function for EPM-T312 and EPM-T322

Which products are affected?
EPM-T110 (CAN Gateway V1.3)
EPM-T111 (CAN Gateway ECO V1.2)
EPM-T312 (4× analog input ±20mA)
EPM-T322 (4× analog output 0...20mA)

Function description
The CAN Gateway has been extended by the following signal function:
3Bhex for EPM-T312 (= Signal function 3Ahex: Current measurement ±20mA)
01hex for EPM-T322 (= Signal function 06hex: Current signal output 0…20mA)

Applications
The CAN Gateway cannot clearly identify the modules EPM-T312 and EPM-T322. The CAN Gateway only recognizes that an analog input/output module is used. In case of analog input modules a default setting of 3Bhex is specified. In case of analog output modules a default setting of 01hex is defined. The new signal functions mentioned before are only supported by the two analog modules if the new CAN Gateway version is used.