¨Safely limited speed¨ function does not work if the shift factor has been changed

Which products are affected?
All 9400 HighLine with SM301 (hardware version VA)

What happens?
The safety module may indicate the error message 'Safe speed invalid'.

When does the problem occur?
If the shift factor under C00100 has been set unequal 16 the 'Safely limited speed' operation mode cannot be used.

Possible diagnostics?
Read out code 100 by means of the keypad.

Short-term measures/recommendations?
Set code 100 to 16.

Evaluation:
It must be observed that neither an extension of the travel range nor an increase of the resolution in the application is required when the 'Safely limited speed' safety function is used. These aspects can only be implemented by changing the shift factor.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200703970/1/