Error message ¨Timer not defined in automatic operation¨(elimination)

Which products are affected?
ESP-HMI1-P (HMI Designer Version 1.7)
EPM-H310 (Text display)

Eliminated function restriction:
If an HMI project (Project Manager – Menu Extras>Convert) of any keypad (e. g. H315) is converted into one for the H310, the number of the available timers is adapted automatically to the corresponding keypad.
This means that after a conversion from the H315 into the H310 the number of available timers is reduced from 32 to 20. If a timer with a number larger 20 (e. g. timer number 31) has been used in a HMI project before the conversion this timer will be deleted after conversion. In this case the following error message is displayed correctly when a HMI project is compiled:

Timer not defined in automatic operation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200600092/1/