EEr trip: Faulty activation immediately after mains connection (elimination)

Which products are affected?
9300 vector 0.37…90 kW SW V7.1

Eliminated function restriction?
An OU message will now only be evaluated after initialisation phase, i.e. from that moment when the drive controller can theoretically be released. As a result, an OU message cannot occur erroneously during the initialisation phase and a faulty EER trip cannot be activated when linking MONIT-OU to DCTRL-TRIP-SET.