Parameter setting with GDC

Which products are affected?
Starttec, all designs, SW version 1.3 and GDC (SW ≤ V4.6)

What happens?
The 4 parameter sets cannot be parameterised with GDC.

When does the problem occur?
The problem occurs when you try to modify the codes of the parameter sets with GDC (SW ≤ V4.6).

Possible diagnostics?
A sensible parameter setting is not possible with GDC (SW ≤ V4.6).

Short-term measures/recommendations?

1. Parameter setting with GDC ≥ V4.7 (update of device file (PDB file) included)
2. Update of the pdb device files for the starttec (see device data update)
Evaluation:
A sensible parameterisation of the 4 starttec parameter sets is not possible with the GDC (SW ≤ V4.6).

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200500053/1/