Remedied from?
GDC 4.7 and GDC easy 4.7
Behaviour of the new version?
If a PID controller without precontrol and with a fixed setpoint is selected from C0181 (Set 2) in the commissioning assistant, the automatic DCB-threshold under C0019 is set to 0 Hz. The process control works without any problems.
Which products are affected?
GDC 4.6.1 and GDC easy 4.5
What happens?
If a PID controller without precontrol and with a fixed setpoint is selected from C0181 (set 2) in the commissioning assistant, the automatic DCB-threshold under C0019 is not set to 0 Hz. As a result, the process control does not work.
When does the problem occur?
The problem occurs if a PID controller without precontrol and fixed setpoint is selected from C0181 (set 2) in the commissioning assistant.
Possible diagnostics?
If code C0019 is not set to 0 Hz after commissioning carried out by making use of the commissioning assistant (with the selections described), this may indicate that the faulty behaviour described before has occurred.
Short-term measures/recommendations?
When closing the commissioning assistant the value 0 Hz can be parameterised under C0019.
The error has been eliminated with GDC 4.7 and GDC easy 4.7.