PEr error after reset (remedied from B-SW V6.5)

Remedied from:
ECS axis module B-SW  V6.5

Behaviour of new version?
The PEr error does not occur anymore after a TRIP reset of the drive controller.



Which products are affected?
ECS axis module B-SW V3.0

What happens?
The PEr error occurs after a TRIP reset.

When does the problem occur?
Sporadically, when using the L_FWM function block for errors, warnings and messages.

Possible diagnostics?
None.

Short-term measures/recommendations?
Do not use the L_FWM function block.

Evaluation:
The error message does not occur if the L_FWM is not used.

Published with service message No. 2004/26 and 2004/27