Operation with 2133, status bit for n=0 is not processed (modification not planed)

Eliminated as of:
There are currently no plans to make any changes.




Which products are affected?
Axis module ECSxA series, operating software V8.3

What happens?
The status bit for n=0 in the DriveCom status word is not processed and is not set permanently.

When does the problem occur?
Always.

Possible diagnostics?
The bit is neither set during standstill.

Short-term measures/recommendations?
None.

Evaluation:
An evaluation of the status bit (e. g. via a superimposed control) may lead to a wrong response by the control.
There are currently no plans to change the behaviour of the operating system.