Parameter transfer via Global Drive Control (elimination)

Which products are affected?

8200vector 0.25 - 90 kW (≥ SW 3.5) with standard I/O
8200motec 0.25 - 7.5 kW (≥ SW 3.5) with standard I/O

Eliminated function restriction?

Transferring parameter sets to the device via GDC was impossible, when the parameter set changeover was configured and active at the same time (e. g. parameter set 2). In this case, the parameter set transfer was aborted and the device indicated a 'CCr' trip or a 'CE5' trip. The communication between GDC and controller was interrupted.  In case of the basic device this deficiency has been eliminated but it still exists when using an application I/O.