Wire-breakage monitoring for the analog input (elimination)

Which products are affected?

8200vector 0.25 - 90 kW (≥ SW 3.5) with standard I/O or application I/O (≥ SW 3.5)
8200motec 0.25 - 7.5 kW (≥ SW 3.5) with standard I/O or application I/O (≥ SW 3.5)

Eliminated function restrictions:

Because of tolerances, the wire-breakage monitoring of the setpoint input for the master current (4 to 20 mA) already triggered an SD5 trip (wire breakage) at master current values above 4.3 mA. Now, this is not possible anymore.