Faulty response of the touch probe input

Which products are affected?

EVS93xx-EI (Servo PLC version 2.1)
EVS93xx-ET (Servo PLC version 2.1)

What happens?

Although the negative signal (C0912 = 1) has been activated for the touch probe input (terminal X5/E4) the touch probe responses on both signals. After several homing operations with function block L_REF the input E4 does not respond to the touch probe signal anymore.

When does the problem occur?

The homing modes 0, 1, 8 or 9 are set at the input 'byHomingMode' of function block L_REF. The homing function is carried out by means of a homing switch (TP-Select: C0911 = 1). The negative signal of the touch probe signal is activated (C0912 = 1).

Possible diagnostics?

None.

Short-term measures/recommendations?

The error only occurs if a control reset will be carried out via the Drive PLC Developer Studio software. In order to avoid this error carry out a mains connection of the control instead of the control reset.