2-pole mains supply for 8200 vector with 3-phase 230 V mains input

Question:

Can the 3x 230 V frequency inverter 8200vector be operated on a 1-phase (2-pole) mains supply?

Answer:

Yes, if the motor power is reduced and the following conditions are observed:


TypeMains currentMains choke 2-poleMotor rated current (8 kHz)Motor rated power
E82EV402K2B22 A1x 22 A, 1x 2 mH12.0 A3.0 kW
E82EV552K2B30 A1x 30 A, 1x 1.5 mH16.0 A4.0 kW
The mains infeed is at terminals L1 und L2. The above-mentioned mains choke always has to be connected in series with L1. There are no other reasonable assignments. Higher levels of motor power are not possible.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/20020404/1/