Corrected from:
Library: L_CT1P_ControlToolBox V03.14.01.07
Response of the new version:
Via 'xValid' output = TRUE, valid values are indicated even if 'lrThresholdValue' is set to the default value of 30 %.
What happens?
'L_CT1P_OnlineIdentStiffMechanics' FB:
During operation, valid values are only indicated via the 'xValid' output = TRUE, if 'lrThresholdValue' is set between 99...100 %.
When does this behaviour occur?
The behaviour occurs if the 'lrThresholdValue' threshold for the 'L_CT1P_OnlineIdentStiffMechanics' FB is set to a value lower than approx. 98%.
Which products are affected?
Library: L_CT1P_ControlToolBox
Short-term measures:
None.