Corrected from:
- Library: L_MC2P_MotionControlCam (FAST Motion) from V03.13.00.52
(contained in the PLC Designer from V03.13.00)
Response of the new version:
The tappet output works as expected even if "lrReactTimeOn" is set to a value other than zero.
What happens?
L_MC2P_TappetRegister: Two edges are output per tappet.
When does this behaviour occur?
TappetRegister with time-controlled tappet output and "lrReactTimeOn" set to a value other than zero.
Which products are affected?
- Library: L_MC2P_MotionControlCam (FAST Motion)
(contained in the PLC Designer)
Short-term measures:
For time-controlled tappets, set lrReactTimeOn to zero.
Evaluation/recommendations: