L_MC2P: xEndOfProfile is sporadically not detected. This has an effect on further profile processing (corrected from V3.10.0)

Corrected from:
 - Library: L_MC2P_MotionControlCam (FAST Motion) V03.10.00.56
                        (contained in PLC Designer from V03.10.00)  

Response of the new version:
The profile end (EnxEndOfProfile) is detected correctly and profile processing works correctly. 
 
What happens?

The profile end (EnxEndOfProfile) is sporadically not detected correctly. As a result, profile processing does not work correctly.

When does this behaviour occur?
The behaviour occurs if CAM profiles are processed in succession, e.g. using the FlexCam technology module (TM).
 
Which products are affected?
- Library: L_MC2P_MotionControlCam (FAST Motion) 
                       (contained in the PLC Designer)
 
Short-term measures:

Set the reference to relative (xMasterAbsolute = FALSE).

Evaluation/recommendations:
 