L_TT1P_TablePositioningBase: Error message Error 1 (corrected from V3.10)

Corrected from:
L_TT1P_TechnologyModules_LM V3.10.0.8

Response of the new version: 
Profile selection from the visualisation works properly. When selecting a profile outside the parameterised range, the "InvalidProfile" error message will be output.
_______________________________________________________________________________________________ 

What happens?
When starting a profile (xExecutePositioning = TRUE), the TablePositioning technology module changes to error status "1". 

 
When does this behaviour occur?
The behaviour occurs if a profile (eProfileNumber) is selected from the integrated visualisation. "0" is assigned to the "eProfileNumber" input of the L_TT1P_TablePositioningBase technology module.
 
Which products are affected?
L_TT1P_TablePositioningBase function block from L_TT1P_TablePositioning_LM library (V3.9.0.21 and higher)
 
Short-term measures:
Only select profiles from the PLC application and ensure that a valid value is used (1-15).
 
 
Evaluation/recommendations:
Profile selection from the visualisation is currently not effective. The profile selected via the PLC application will always be used.
 