L_SMC_AxisBasicControl: xIsHomed remains TRUE (eliminated from V3.3.2)

Corrected from:
PLC Designer V3.3.2
Library L_SM3_DriveUtil V3.3.2.0

Behaviour of the new version?
In the case of a resolver error, the output xIsHomed of the L_SMC_AxisBasicControl function block turns FALSE.



What happens?
In spite of a resolver error, the output xIsHomed of the L_SMC_AxisBasicControl function block remains TRUE.

When does the problem occur?
If the axis is referenced, the output xIsHomed at the L_SMC_AxisBasicControl function block turns TRUE. If a resolver error occurs then, the output remains TRUE.

Which products are affected?
PLC Designer from V3.3
L_SM3_DriveUtil library from V3.3.0.0

Diagnostics options?
None

Short-term measures/recommendations?
None

Evaluation:
Via the output xIsHomed it is not detected that a resolver error has occurred, and thus the reference is lost.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201208922/1/