L_TS2P_CrossCutter: "MasterOutOfCam" error (22025) during touch probe after trimming (fixed as of V3.31.1)

     

Fixed as of: 

L_MC2P_MotionControlCAM (in V3.31.1 and V3.33.0 and later)


Behavior of the new version: 

In the new version, no error is triggeredif the conductance was previously set via the offset lrSetOffsetPosX in such a way that the resulting value of the X-axis lies within the valid cam disc range .

In this case, the cam is started correctly and run through completely.

Description of behavior: 

When the cam disc is started, the technology module (TM) enters an error state. The error message

eErrorID = 22025 – MasterOutOfCam

is displayed.

Conditions under which the behavior occurs: 

The error always occurs when the conductance is outside the valid cam profile range at the start of the cam profile.
This also happens if the conductance was previously adjusted by the offset lrSetOffsetPosX such that the resulting value of the X-axis is again within the cam range.


Affected products: 
Library L_TS2P_TechModulesSynchronizingCamming

 

Short-term measure, recommendations, assessment: 

By adjusting or stretching the cam on the X-axis, the valid range can be expanded so that the reference value is always within the cam at the start.

[Automatic Translation]