RETAIN data is not initialised when downloading projects (corrected from V3.12)

Corrected from:
PLC Designer V3.12
 
Response of the new version:
Irrespective of the use of the L_Util_Retain function block, the RETAIN data is reset to its initialisation values when downloading projects.
 
What happens?
After downloading a project, the RETAIN data is not reset to its initial values but maintains the values available before the project download.
 
When does this behaviour occur?
The above-described behaviour occurs when using the L_Util_Retain function block from the L_Util library in a project to safe the RETAIN data additionally on an SD card (e.g. for device replacement).
 
Which products are affected?
PLC Designer from V3.2
 
Short-term measures/recommendations:
After downloading your project, carry out the 'Online > Reset cold' menu command to reset the RETAIN data.
 
Evaluation:
When downloading projects and using the L_Util_Retain function block, the RETAIN data is not reset to its initialisation values. Use the 'Reset cold' menu command to reset the RETAIN data.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500523/1/