L_TT1P_RegisterControl: Selecting the "eSourceForCorrWindow = Master" parameter has no effect (eliminated from V3.10)

Eliminated from:
L_TT1P_TechnologyModules_LM V3.10.0.8
 
Behaviour of new version:
The correction window is only used for the master axis. 
 

What happens?
The eSourceForCorrWindow parameter is used to select the reference position of the correction window (lrLowerCorrPos, lrUpperCorrPos). The parameter for applying the correction window to the master axis (eSourceForCorrWindow = Master) does not work correctly. The correction window refers to the slave position and is opened and closed at a wrong position. The function cannot be used appropriately.

When does this behaviour occur?
The behaviour occurs if the eSourceForCorrWindow parameter (in the scPar parameter structure of the technology module) is set to "Master". 
 
Which products are affected?
L_TT1P_RegisterControl technology module in L_TT1P_TechnologyModules_LM library (V3.9.0.62 and higher)
 
Short-term measures:
Only select "eSourceForCorrWindow = Register".
 