Homing: Reference is set at unexpected limit switch (eliminated from V5.0 onwards)

Eliminated from:
HighLine with firmware version V05.01 or higher

Behaviour of the new version?
The unexpected limit switch is not evaluated and the drive continues to rotate until the correct limit switch is activated.



Which products are affected?
8400 HighLine with FW < 05.01

What happens?
The home position cannot be found because the homing process is interrupted by the unexpected limit switch.

When does the problem occur?
If an 'incorrect' limit switch is activated during Homing to hardware limit switch, the controller triggers the set error response (in the basic TroubleQSP setting).

Possible diagnostics?
Check whether the motor triggers an error response if an incorrect limit switch is activated during homing.

Short-term measures / recommendations?
None

Evaluation:
The error triggered by mistake can be acknowledged. Homing can be continued.

Information taken from chapter 1.1.24 of Service Message No. 16/2010.