Unexpected Logbook entries in case of fan errors (eliminated from V5.0 onwards)

Eliminated from:
StateLine / HighLine with firmware version V05.01 or higher

Behaviour of the new version?
This function restriction is eliminated with the above-mentioned firmware version.



Which products are affected?
8400 StateLine / HighLine with FW < 05.01

What happens?
Unexpected Logbook entries in case of fan errors

When does the problem occur?
If a heatsink temperature of 60 °C is reached in devices which do not have interior / heatsink fans, a fan error is displayed although fans are not available.

Possible diagnostics?
The error occurs although fans are not available in the device.

Short-term measures / recommendations?
Set the fan monitoring response in C0566 to No Reaction.

Evaluation:
In the default setting, the response to fan failure is configured as Warning (C0566). The device displays the warning and generates a Logbook entry but the drive behaviour is not affected.

Information taken from chapter 1.1.14 of Service Message No. 16/2010.