Task Overrun of PLC_PRG when deleting a breakpoint (elimination)
Which products are affected?
EVS93xx-EI (Servo PLC Version 6.5 DSMC control board)
EVS93xx-ET (Servo PLC Version 6.5 DSMC control board)
EPL-10200 EI (Drive PLC Version 6.5)
Eliminated function restriction:
A Task Overrun of the cyclic task 'PLC_PRG' does not occur anymore when using breakpoints.
Which products are affected? EVS93xx-EI (Servo PLC Version 6.2 DSMC control board) EVS93xx-ET (Servo PLC Version 6.2 DSMC control board) EPL-10200-EI (Drive PLC Version 6.2)
What happens? A Task Overrun of the cyclic task PLC_PRG occurs. The response of the target system can be defined individually in DDS under -> Project -> Exceptional response. Trip, warning or interference/QSP are possible responses.
When does the problem occur? The problem only occurs when using breakpoints. If the PLC program stops at a breakpoint during the processing and if this breakpoint is deleted afterwards, the problem occurs when restarting the PLC.
Possible diagnostics? None.
Short-term measures/recommendations? None.
Evaluation: The error can be avoided if the user does not use breakpoints.