c250-s: Password-protected boot application, general device reset does not work properly

Corrected from: Plc Designer V03.16.0

Response of the new version:
No error message is displayed when the “Delete” function is executed.
 
What happens?
Performing a general reset for password-protected boot applications results in an error message.
 
When does this behaviour occur?
The behaviour occurs if the boot application is protected by a password and the general reset command is executed.
 
Which products are affected?
Safety Controller c250-S, Plc Designer V03.14.0


Short-term measures:
NONE
 
Evaluation/recommendations:

Interrupt the controller connection. Wait until the error message appears. Restart the controller. Load the projects again onto the Safety Controller c250-S.

 