DDH (Drives Datahub) - for i5x0 and 8400: does not support the oscilloscope's variable trigger
Fixed as of: DDH V1.6
Behavior of the new version:
The oscilloscope is recorded when the trigger value of the variable is reached.
Description of behavior:
Variable triggering is not supported when using i5x0 and 8400 oscilloscope recordings. If variable triggering is configured in EASY Starter, the "Forces trigger" (default) is used instead. This means that an oscilloscope recording starts immediately.
Conditions under which this behavior occurs:
There are no specific conditions required for this behavior to occur.
Affected products:
DDH V1.3..0
Short-term measures, Recommendations, Assessment:
The selected trigger variable must also be selected in the
recorded channels. This allows it to be used as a trigger
as well.
In the example: The trigger variable is configured as Channel 3
.