Exception when inserting a machine module (corrected from V3.17)

Corrected from:
PLC Designer V3.17
Standard ApplicationTemplate project template V3.17 and higher
 
Response of the new version:
When inserting a new machine module in the 'Insert Machine Module' dialog, the 'MM_' name can be entered in the User defined name field without triggering an exception.
 
What happens?
An unhandled exception occurs when inserting a new machine module.
 
When does this behaviour occur?
When inserting a new machine module (context menu command Insert Empty Module) in the 'Insert Machine Module' dialog, an exception occurs after entering the 'MM_' name in the User defined name field.
 
Which products are affected?
PLC Designer V3.13
Standard ApplicationTemplate project template from V3.13
ApplicationTemplate_PackML project template from V3.9 
 
Short-term measures:
Do not start the 'User defined name' of a machine module with the string 'MM_'.
 
Evaluation/recommendations:
The name of a machine module is composed of the string 'MM_' and the name entered in the User defined name field (e.g. MM_MachineControl). If the 'User defined name' already starts with 'MM_', this will lead to an exception.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201700266/1/