L_TT1P_TablePositioning: When positioning is aborted with xAbortPositioning, the drive decelerates with the parameters of xHalt (corrected from V3.12)

​Corrected from:
L_TT1P_TechnologyModules_LM library V3.12.0.9

Response of the new version: 
When a profile is aborted, the drive decelerates with the profile data of the currently selected profile.
                                                                                                                                                                

What happens?
When positioning is aborted, the drive decelerates with the parameters of the "Halt" function. Positioning is expected to be aborted with the current profile parameters.

When does this behaviour occur?
The behaviour occurs when positioning is aborted with xAbortPositioning.
 
Which products are affected?
L_TT1P_TablePositioningBase function block from the L_TT1P_TechnologyModules_LM library (V3.10.0.8 and higher)
 
Short-term measures:
The deceleration parameters of the "Halt" function can be used to abort positioning.
  
Evaluation/recommendations:
In future, the parameters of the active profile shall be used to abort positioning.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500631/1/