Which products are affected?
EPL-10200 (Drive PLC V8.1)
EVS93xx-EI (Servo PLC V8.0)
EVS93xx-ET (Servo PLC V8.0 with technology function)
Eliminated function restriction:
An activated node guarding event (C0168 = 260) can be reset. In response to a node guarding telegram the PLC target system changes the toggle bit included correctly.
Which products are affected? EPL-10200 (Drive PLC V7.1 and lower) EVS93xxEI (Servo PLC V7.2 and lower) EVS93xxET (Servo PLC with technology function V7.2 and lower)
What happens? In response to a node guarding telegram the PLC target system does not change the toggle bit accordingly. An activated node guarding event (C0168 = 260) can only be reset by mains switching.
When does the problem occur? The response described occur may occur in case of a high bus load on the system bus if the PLC target system has been configured as Slave with node guarding (C0352 = 4).
Possible diagnostics? None.
Short-term measures/recommendations? None.
Evaluation: The function restriction may occur in case of a high bus load on the system bus if the PLC target system has been configured as Slave with node guarding.