No PDO receipt of data after program download (elimination)
Which products are affected?
EVS93xx-EI (Servo PLC, software version 2.3)
EVS93xx-ET (Servo PLC, software version 2.3)
EPL 10200 (Drive PLC, software version 6.1)
Function restriction corrected
Data of external devices can be received after a DDS project download via function block L_CanPdoReceive.
Which products are affected?
EVS93xx-EI (Servo PLC version 2.x and 6.0)
EVS93xx-ET (Servo PLC version 2.x and 6.0)
EPL-10200 (Drive PLC version 2.x and 6.0)
How is the reaction? With function block L_CanPdoReceive from the library LenzeCanDrv.lib no data can be received.
When does the problem occur? After a DDS-project download it can happen that with the function block L_CanPdoReceive no data can be received.
Possible diagnostics? No.
Short-term measures/recommendations? If after a DDS-project download a mains connection of the control follows, data can be received with the function block L_CanPdoReceive.