No PLC_PRG process image when starting the PLC (elimination)
Which products are affected?
EVS93xx-EI (Servo PLC Version 6.3 DSMC control board)
EVS93xx-ET (Servo PLC Version 6.3 DSMC control board)
EPL-10200-EI (Drive PLC Version 6.3)
Eliminated function restriction:
The PLC_PRG process image is always generated correctly.
Which products are affected? EVS93xx-EI (Servo PLC Version 2.3) EVS93xx-ET (Servo PLC Version 2.3) EPL-10200 (Drive PLC Version 6.1)
What happens? When the PLC is started, a process image is not generated for the PLC_PRG for several cycles.
When does the problem occur? The problem occurs on system modules (module numbers < 100) which are only used in the PLC_PRG.
Possible diagnostics? The file 'Process image' (under Object Resources) shows if the process image is generated in the cyclic task and the module number of the system module used.
Short-term measures? None.
Evaluation: The error is not critical since the time response of the PLC_PRG is not constant due to the multi-tasking.