i750: Activate quick stop (QSP) via digital input of the inverter (DI) (from V01.04.00)
Function extension: The CiA quick stop function (QSP) can now also be controlled via a digital input on the inverter (DI) if required. The following objects are available for parameterization:
0x2632:x Inversion of logic
0x2633:x Debounce time
0x263B:x Manually control digital input
0x282C:1 Application Level Digital Inputs
0x2DE1:002: CiA402: QSP via DIGIN Enable
The two control signal sources for activating the quick stop function (digital input and control bit in control word 0x6040) are OR-linked.
Included in the following products: Servo Inverter i750 FW: from V01.04.00
Application: applications in which the quick stop function (QSP) is to be activated via a digital control input directly on the inverter.