Corrected from:
Behavior of the new version:
If an application is downloaded to the safety controller and a boot
application is created, communication with the PLC Designer is interrupted.
The safety controller then crashes every time the boot application is
started.
Index 0x2230 (Free Disk Space) displays 0 kB in all subindices.
Conditions under which the behavior occurs:
The behaviour occurs when FBs in an Extended POU are instantiated very
often (approx. 1500 times). Depending on the number of FB calls, different
application runtimes occur for both microcontrollers until a timeout error
occurs. This is the case if the two runtimes differ by more than 1 ms.
The memory requirements and the cycle time of the safety programme are not
relevant.
The current number of instances cannot be displayed in the PLC Designer,
but must be kept in view during programming.
Affected products:Safety-Controller
C25BAYSQ
Short-term measures, Recommendations, Rating:
Download
the project to the safety controller without creating a boot application. The
boot application should only be created once it has been ensured that the
safety controller can process the programme.
If the
language range is sufficient, use a Basic POU.
If the
error has occurred, the safety controller must be sent to Lenze Service for
repair.