IO-1000: Error messages when translating the PLC project

Corrected from:
Device description for Controller 3200C FW V03.21.00
Device description for Controller p500 FW V03.21.00
Device description for Controller p300 FW V03.21.00
Device description for Controller c300 FW V03.21.00
Device description for Controller c5x0 FW V01.07.00
Device description for Controller c750 FW V01.07.00

Response of the new version:
With this device description of the controller, the error messages no longer occur.
The current device descriptions of the EPM-S131 and the attached IO modules can be used.

What happens?
When translating the PLC Designer project, the error messages appear:

     EPM-S131
     [ERROR] C0077: Unknown type: 'L_ECC.L_ETCSlave_S131'.
     [ERROR] C0077: Unknown type: 'L_ECC.L_IOSlice'
     [ERROR] C0035: Programme name, function or function block instance expected instead of 'EPM_S131.CyclicCall'.

     IO-1000 Module
     [ERROR] C0077 Unknown type: 'L_ECC.L_IOSlice'.

     Especially when using the EPM-S604
     After updating to V1.0.0.6, the error message "Incomplete device description" appears on the EPM-S604.
     Fehlermeldung_Unvollständige_Gerätebeschreibung_EPM-S604.png

When does the behaviour occur?
A PLC Designer project with one of the following device descriptions is used
Device description for Controller 3200C <=FW V03.20.01
Device description for controller p500 <=FW V03.20.01
Device description for controller p300 <=FW V03.20.01
Device description for Controller c300 <=FW V03.20.01
Device description for controller c5x0 <=FW V01.06.01
Device description for controller c750 <=FW V01.06.01

An EPM-S131 with the latest device description is attached to the EtherCAT master of the controller.
Or one of the IO-1000 modules with the latest device description (see PDF, column "Yes, from version") is attached to an EPM-S130 / EPM-S131.

Which products are affected?
IO-1000 EtherCAT Bus Coupler EPM-S130 / EPM-S131 / IO-1000 modules

Short-term measures:
The EPM-S131 with the device description V1.105.0.0 can be used in the PLC Designer project. This means that the described error messages do not occur.
Furthermore, the IO modules attached to the EPM-S131 must also use an older version (device description of the IO modules in the PLC Designer project).
The device description of the attached IO modules must correspond to the version status in the column "No, until Version" or older in the list IO-1000 versions with reference to Fast Framework.pdf.
The device descriptions in the column "Yes, from version" or newer cannot be used in this case.

In the case of an EPM-S130, the IO modules must also correspond to the version status in the column "No, until version".