L_TB2P_AxisInterface: Output values are too small by a factor of 1000 (corrected from V3.26.0)

Corrected from:
Library L_TB2P_TechModulesBasic (from V03.26.00)
(Update via Easy Package Manager)

Response of the new version:
The following outputs of the function module L_TB2P_AxisInterface give their value in the resolution of the parameters from which they are read.
-    lrActualMotorCurrent --> Actual motor current in % with 1 decimal place
-    lrThermalLoadDevice --> Ixt load without decimal place
-    lrThermalLoadMotor--> I²xt load without decimal place

What happens?
The following outputs of the function block L_TB2P_AxisInterface are scaled too small by factor 1000.
 -    lrActualMotorCurrent --> Actual motor current in % scaled too small by factor 1000. 4 decimal places
-    lrThermalLoadDevice --> Ixt load with 3 decimal places.
-    lrThermalLoadMotor--> I²xt load with 3 decimal places

When does the behaviour occur?
When these outputs of FB L_TB2P_AxisInterface are used.

Which products are affected?
Function module L_TB2P_AxisInterface from library L_TB2P_TechModulesBasic  

Short-term measures:
None

Evaluation / recommendations: