PLI: Start via parameter 0x2C63:1 and parallel via operating mode 0x6060 incorrectly leads to error message 'Motor phase failure'. (corrected from V01.08.00)

Corrected from:
Servo-Inverter i950 FW: from V01.08.00
 
Response of the new version:
An interlock has now been implemented so that the pollage identification function is no longer started in parallel as described. Starting the PLI via operating mode 0x6060 now has priority over the PLI setting under parameter 0x2C63. The erroneously displayed error message no longer occurs.

 
What happens?
If polling identification is started in parallel by parameter and by operating mode, the error message 0xxxxx "Motor phase failure" is output incorrectly, despite correct wiring.

When does the behaviour occur?
  • PLI activated on controller enable via parameter 0x2C63:1 = [1] or 0x2C63:1 = [2] AND
  • Operating mode 0x6060 = [-12] "Pole position ident. is set.

Which products are affected?
Servo-Inverter i950 FW
 
Short-term measures / Evaluation / recommendations:
Before executing the PLI via the operating mode 0x6060 = [-12] "Pole position ident. first make sure that the PLI is not already being executed by setting parameter 0x2C63:1. If necessary, set parameter 0x2C63:1 = [0] to deactivate execution.