Module parameters of the CANopen bus coupler EPM-S110 are not taken over

Corrected from: 
Device description EPM-S110 V01.14.0.5 contained in I_O-System 1000_ CAN V3.x (1.6).lpk
(Update via Easy Package Manager)

Response of the new version:
Default value of parameter 0x31FF:0 is 255 (accept module parameters). This means that the set module parameters are automatically accepted.

What happens?
The set module parameters (e.g. for the analogue modules) are not accepted. The parameters of the factory setting are active.

When does the behaviour occur?
In the PLC Designer project, a question mark (?) is entered as the value for parameter 0x31FF:0.
 
Which products are affected?
PLC Designer from V3.0
EPM-S110 (I/O1000 CANopen bus coupler)

Short-term measures:
The parameter 0x31FF:0 is to be changed to the value 255 (Accept Moduleparameter). The respective module parameters are then accepted.

Evaluation / recommendations: