The bus configuration error described above occurs when
an EtherCAT device description (*.xml) was created from a PLC Designer project of a Servo Inverter i950 (i950 User TA) via EASY Export,
this is attached in a PLC Designer project of one of the Lenze controllers listed below as an EtherCAT slave and
the firmware of the i950 connected to the controller is not equal to the firmware version selected in the project from which the device description was generated (see first point).
Which products are affected?
Cabinet Controller c300
Cabinet Controller 3200C
Panel Controller p300
Panel Controller p500
Short-term measures:
If the error message occurs after replacing the i950 servo inverter, use the EASY Firmware Loader to load the firmware version that the replaced i950 has into the new i950 servo inverter. In the above example, firmware version 1.4 (compare 0x10401 in the above message) is to be loaded into the i950.
When creating a PLC Designer project or when revising a project, remove the XML attribute 'CheckRevisionNo="EQ_OR_G"' from the EtherCAT device description created via the EASY export before installing it in the device repository of the PLC Designer. This change deactivates the version check.
Evaluation / recommendations:
If the firmware version of an i950 servo inverter connected to the EtherCAT interface of a Lenze controller is higher than the firmware version of the device description used in the PLC Designer project, an error message 'Configuration mismatch' occurs when starting the controller. This can happen, for example, when replacing a device. An application solution is described under Short-term measures.