EPM-S13x: The set parameters of the counter modules are not accepted.

What happens?
The set parameters of the counter module (e.g. counter mode, signal evaluation) are not adopted. The previously set values (factory setting) remain visible.

When does the behaviour occur?
The parameters are changed online via the PLC Designer or the parameters are changed offline and the application is transferred to the controller without program download (OnlineChange with or without program change).
 
Which products are affected?
IO-1000 EtherCAT Bus Coupler EPM-S130
IO-1000 EtherCAT Bus Coupler EPM-S131 

Short-term measures:
These parameters can only be changed during a restart of the EtherCAT. After programme transmission via OnlineChange, this can be done, for example, by a reset (warm) or reset (cold).
 
Evaluation / recommendations:
No change is planned for this behaviour.

Automatic Translation