TM Speedcontrol: lrSetPos_Dist does not work in the visualization (corrected from V3.23.0)

Corrected from:
L_TF2P_TechModulesFollowingPositioning  (from V3.23.0.38)
L_TW2P_TechModulesWindingTraversing (from V3.23.0.2)
(Update via Easy Package Manager)

Behaviour of new version:
Wird die Achse mit MoveAbs/MoveRel aus der Visualisierung heraus angesteuert (CtrlBasicMotion), wird der über die Visualisierung eingetragene Wert in SetPos_Dist verwendet.

What happens?
The value entered via the PLC-Designer visualization in SetPos_Dist is not used
 
When does the behaviour occur?
The axis is to be controlled with MoveAbs/MoveRel from the visualization (CtrlBasicMotion).
 
Which products are affected?
Function modules L_TF2P_SpeedControlBase, L_TF2P_TablePositioningBase and L_TF2P_VirtualMasterBase from library L_TF2P_TechModulesFollowingPositioning
Function modules L_TW2P_WinderDancerCtrlState and L_TW2P_WinderTensionCtrlState from library L_TW2P_TechModulesWindingTraversing

Short-term measures:
Wiring of input scCtrlBasicMotion.lrPos_Dist from within the application.

Evaluation/Recommendations: