L_MC1P_SetPosCtrlAdaptValue and i950 TA Cia402-Advanced: VP of the position controller cannot be changed correctly (fixed from V03.23.00)

Corrected from:
Library:  L_MC1P_MotionControlBasic (FAST Motion) from V03.23.00
                (Update via Package Manager)

Response of the new version:
The adaptation of the gain (Vp) of the external position controller in the i950 TA Cia402-Advanced can now be changed as expected using FB 'L_MC1P_SetPosCtrlAdaptValue'.

 
What happens?
i950 TA Cia402-Advanced:
The amplification (Vp) of the position controller cannot be changed from the PLC application in the higher-level controller, using FB 'L_MC1P_SetPosCtrlAdaptValue'.

When does the behaviour occur
  • i950 TA Cia402-Advanced und
  • external position control within the TA Cia402-Advanced and
  • Use of FB 'L_MC1P_SetPosCtrlAdaptValue' on the higher-level controller.
Which products are affected?
Library:  L_MC1P_MotionControlBasic  (FAST Motion)
 
Short-term measures, Evaluation/Recommendations:
Change the Vp gain (Sub 93) of the position controller in the motion axis i950 TA Cia402-Advanced directly by writing to the parameter using FB 'MC_WriteParameter':
Index := 16#500D, Subindex := 93, uiByteLength := 2